INTRODUCING OUR REVOLUTIONARY

EXCOOL FLEX DATA CENTER COOLING SOLUTION

Where Performance, Efficiency, and Innovation Intersect!

Capacity Range

400kW to 700kW (400kW – 600kW – 800kW)

High-Density Cooling Powerhouse

Achieve a best in class 133kW of cooling per linear
meter of wall (50kW/ft) for unparalleled thermal management.

Optimised Energy Utilisation

Experience industry-leading low pPUE, ensuring maximum operational efficiency.

Extreme Environment Adaptability

Engineered for impeccable performance, even in the most challenging ambient conditions.

Zero-Water Cooling Solution

Achieve superior cooling capabilities without consuming a drop of water — the pinnacle of sustainability.

Enhanced System Resilience

Benefit from a one-to-one connection architecture designed to fortify system reliability.

In-Built Controls Redundancy

Our fully enclosed system ensures uninterrupted operation, safeguarding against power inconsistencies.

Swift Cooling Backup

With up to 1-minute cooling back-up during power loss scenarios, minimising operational disruptions.

Turnkey Installation

Supplied with flexible pipework, our units ensure rapid and cost-effective installation.

Quick-to-Market Delivery

Don’t let timelines hold you back; our short delivery windows expedite your project schedule.

Customizable Capacity

Enjoy the freedom to mix and match indoor and outdoor units for an optimised cooling solution tailored to your needs.

Eco-Smart Design

Eliminate the need for glycol between indoor and outdoor units, featuring low GWP refrigerant for a greener tomorrow.

Seamless Infrastructure

Our enclosed data hall airflow negates the need for separate service corridors, streamlining your operational layout.

Easy Maintenance

Designed for straightforward, hassle-free upkeep, ensuring longevity and continuous performance.

Cost-Efficient Investment

With low CAPEX requirements, we provide a financially accessible solution without compromising on quality or functionality.

Elevate your cooling infrastructure to new heights of engineering excellence. Choose the new Excool Flex Data Center cooling solution for an unmatched blend of performance and innovation.

EXCOOL FLEX CHILLER

EXCOOL FLEX PRECISION COOLING WALL (PCW)

Excool Flex PCW

EXCOOL FLEX CHILLER (Imperial)

Free Cooling at 50°C Ambient
520kW
Free Cooling at 61°C Ambient
260kW
Condensing Air Volume
102000 cfm
External Water Pressure Drop
50 ft.w.g
Power Consumption
158kW
Electrical Supply 3phs 3/4wire + E
60Hz/480V
Depth
185 in
Width
90.5 in
Height
108 in
Operating Weight
7937 lbs

EXCOOL FLEX PCW (Imperial)

Max Sensible Cooling Capacity
520kW
Power Failure Redundancy
2 Minutes
Supply Air Volume
76515 cfm
External Static Air Pressure
0.4 in.w.g
Power Consumption
32kW
Electrical Supply 3phs 3/4wire + E
60Hz/480V
Depth
118 in
Width
126 in
Height
199 in
Operating Weight
8818 lbs

EXCOOL FLEX CHILLER (Metric)

Free Cooling at 8°C Ambient
400kW
Free Cooling at 16°C Ambient
200kW
Available External Pressure Drop
150kPa
Voltage
400V
Frequency
50Hz
Phases
3 + N + E
Peak Power Consumption
153kW
Depth
4700mm
Width
2300mm
Height
2750mm
Operating Weight
3600kg

EXCOOL FLEX PCW (Metric)

Sensible Cooling Capacity
400kW
Power Failure Redundancy
2 Minutes
Supply Air Volume
28m3/s
Voltage
400V
Frequency
50Hz
Phases
3 + N + E
Peak Power Consumption
20kW
Depth
3000mm
Width
3200mm
Height
5050mm
Operating Weight
4000kg

Please note this data sheet represents maximum values with all components operating at 100% capacity. This data sheet is not based on any specific outdoor ambient condition.

Excool Flex Power Loss

Excool flex Animation

Excool Flex Dubai